Features of Context Plus XFP502/X/CON Addressable Control Panel
♦ Context Plus XFP502/X/CON Addressable Control Panel
♦ Third-party certificated to EN54 parts 2 and 4 by the LPCB.
♦ Full compatibility
♦ InterConnect Up To Eight XFP Main Panels
♦ Four XFP Repeater Panels Per Main Two Wire RS485 Network.
♦ Two Independently Programmable Conventional Sounder Circuits.
♦ Two Programmable Inputs.
♦ A Fault Output Relay & Three Programmable Relay Outputs With Voltage
♦ Three Zone Dependency Functions (A, B & C to EN54-2 Clause 7.12)
♦ A Day/Night Function.
♦ An Investigation Delay Period Function.
♦ Individual Sensitivity Settings For Each Device
♦ Powerful Short Circuit Protected Loop Drivers
♦ An Integral EN54 Switch Mode PSU rated @ 185-260V a.c. 50/60Hz (3A on 32 zone panel, 1.4A on 16 zone panel)
♦ Earth Fault Monitoring
SPECIFICATIONS: | |
BRAND | Context Plus |
Model | XFP502/X/CON |
Main supply | 230V a.± 10% 50/60Hz. Max current 680mA |
Internal power supply | 27V d.c Nominal |
Total output current limited to | 3A @ 230 V a.c. |
Supply and battery charger monitored for failure | Yes |
Batteries monitored for disconnection and failure | yes |
Batteries protected against deep discharge | yes |
Max. battery size and type | 7.0 Ahr VRLA |
Specified batteries for LPCB approved systems | 2 x Yuasa NP7-12 |
Quiescent current drain (1 loop unloaded) | < 80mA |
Quiescent current drain (2 loop unloaded) | <100mA |
Earth fault monitoring | Yes (any conductor) |
Temperature compensated charging | Yes |
Number of loop drivers | (XFP501/CON) 2 (XFP502/CON |
Line monitored for open and short circuit faults | Yes |
Onboard loop isolators with LED indication when active | Yes |
Auto-polling from each loop en | Yes |
Max. loop output current | 500mA (Voltage: 25V min, 34V max) |
Max. number of addressable devices per loop | 126 |
Number of programmable sounder groups | 16 |
Number of programmable output sets | 16 |
Number of programmable circuits | 2 |
End of line resistor value | Yes |
End of line resistor value | 6800 Ω 5% Tol. 0.25 W |
Line monitored for open and short circuit faults | Yes |
Outputs fused at | 400mA |
Max. number of sounders @ 20mA | 80 |
Type | Relay voltage free single pole changeover |
Max switching current | 1A |
Max switching voltage | 30 V d.c |
Fault | Active when no faults are present |
‘24V’ Aux Power Output | 19.5V min, 28V max. Max current 100mA. Protected by resettable overload circuit |
Input 1 | Connectto 0V to trigger. Max input voltage 27V d.c. (non-latching). Programmable from cause and effect. |
Input 2 | Connectto 0V to trigger. Max input voltage 27V d.c (non-latching). Programmable from cause and effect. |
Mains Fuse | 1A HRC Ceramic 20mm |
Battery Fuse – limits the current drawn from the battery | 3.15A F 20mm |
Control buttons | Silence, Reset, Resound, Investigate; More Information; Menu |
Event scrolling and menu access buttons | Up (1); Down (2); Accept (3); Abort (4) |
Liquid Crystal Display | Two lines x 40 characters, backlit |
Number of Zonal LED indicators | 32 |
Approx. dimensions of back box (W x H x D | 410 x 250 x 80mm (metal) |
Approx. dimensions of lid (W x H x D) | 439 x 274 x 7mm (metal) |
Approx. weight (without batteries) | 4.5kg |
Type of cable | Fire resistant screened cable, minimum size 1mm2 |
Max. cable length per loop | 1km |
Connector blocks | Plug-on type, largest acceptable conductor size 1.5mm2 |
Max. allowable loop impedance (each conductor | 20Ω |
Max. cable capacitance | .27µF |
Connection | Via AFP711 network driver card fitted at main panel |
Temperature range | -5 to +40oC |
Maximum relative humidity | 95% |